Digital Meter / Printer
Digital Integrating Flow rate Meter
MODEL 419B
- ■ DIN 48x48 mm compact size
- ■ Dual Display of flow rate and totalizer
- ■ Pulse output for total and 2 x preset output
- ■ Pulse input of 419B and analog input of 419A can be linked in series
Model Designation
419B | - | □ | - | □ | - | □ | - | □ |
① | ② | ③ | ④ |
①Measuring input
Code | Measuring range | Input specifications |
---|---|---|
Blank | Non-voltage output or open collector | DC 12 V, 10 mA |
RE | Voltage pulse | "H" = 4.5 to 30 V
"L" = 0 to 2.0 V Approx. 5 kΩ |
MG | Tachogenerator | AC 0.8 to 80 Vp-p |
SN | Sine wave | AC 0.1 to 20 Vp-p |
②Power supply voltage
Code | Power source voltage |
---|---|
A | AC 100 to 240 V |
8 | DC 12 V ±10% |
9 | DC 24 V ±10% |
③Power source for sensor
Code | Output voltage | Output current | Ripple |
---|---|---|---|
Blank | Not available | ||
3 | 12 V ±5% | 60 mA | Less than 5% |
5 | 24 V ±5% | 30 mA | Less than 5% |
④Analog output, RS-485
Code | Output specifications | Output impedance | Tolerable Load resistive |
---|---|---|---|
Blank | - | ||
03 | DC 0 to 1 V | Approx. 0.1 MΩ | More than 200 Ω |
04 | DC 0 to 5 V | More than 1 kΩ | |
05 | DC 0 to 10 V | More than 2 kΩ | |
09 | DC 1 to 5 V | More than 1 kΩ | |
29 | DC 4 to 20 mA | 5 MΩ | 0 to 500 Ω |
E1 | RS-485 | - |
Basic Specifications
Flow indication | 0 to 9999: Red LED, Character 8 mm High, with zero-suppress function. Decimal point: Programmable form the front key Over-range display: Display blank: Changeover to be put on or off. |
---|---|
Display cycle | Selectable from the front key. 100ms, 400ms, 1s, 2s, 5s |
Moving averaging | Selectable from the front key. 1, 2, 3, 4, 8, 16-time |
Pulse conversion value | Selectable from the front key, from 1x10-6 to 9999 |
Time base | Selectable from the front key. Seconds, minutes, or hours |
Accuracy | ± (0.05%+1digit) |
Flow indication | 0 to 99999: Green LED, Character 8mm High, with zero-suppress function. 5 or 10 significant digit: Programmable form the front key Over-range display: Display blank: Changeover to be put on or off. |
---|---|
Pulse factor | Programmable Pulse factor from the front panel. From 1x10-6 to 999,999 pulses/unit. P.O output is synchronized to input pulse when exceeding 1. |
Primary integrated value | from 0 to 99999, programmable from the front key |
Display cycle | approx. 0.1s |
SIG display | Light-up when inputting the signal |
Input Frequency | HF range: 0.01 Hz to 10 kHz LF range: 0.01 Hz to 100 Hz Programmable from the front key. |
---|---|
Min. Pulse width | HF range: 0.05ms / LF range: 5ms |
Latch / Pause input | Latch:
Hold display of instantaneous and integrating flow rate, and data output (except of Simultaneous pulse output). Accumulated integrated count will be operated. Pause: Hold display of instantaneous and integrating flow rate, and data output. Accumulated integrated count will be temporarily stopped. Non-voltage contact or open collector (NPN) DC 5 V, 10 mA Active "L", "L" = 0 to 1 V, "H" = 3.5 to 5 V, 10ms min. Pulse width. |
Reset | reset to 0 or primary setting value |
Backup | An EEPROM retains the data of accumulated total flow when the power is interrupted. Keep 10 years. |
Output | relay contact: AC/DC 150 V, 80 mA |
Noise filter | 1000 V against the power line noises |
Withstand Voltage | Input terminals - External case: AC 1500 V each for 1min. Power supply terminals - External case: AC 1500 V each for 1min. Power supply terminals - Input and Output terminals: AC 1500 V each for 1min. Input terminals - Output terminals: AC 500 V each for 1min. |
Insulation Resistance | DC 500 V, More than 100 MΩ |
Power Supply | AC 100 to 240 V (50/60 Hz), DC 12 V ±10%, DC 24 V ±10% |
Allowable power | AC 90 to 250 V (50/60 Hz), DC 10.8 to 13.2 V, DC 21.6 to 26.4 V |
Power Consumption | Approx. 7.5 VA at AC 100 V, 10 VA at AC 200 V, 400 mA at DC 12 V, 250 mA at DC 24 V. |
Operating Temperature | 0 to 50°C |
Storage Temperature | -20 to 70°C |
Weight | Approx. 160 g |