Our Technology, solution for Tomorrow too!

Digital Meter

Available Product Type

416B:
AC input
416C:
Receiver
416D:
DC input
416K:
AC (RMS)

DC/AC Voltmeter, DC/AC Ammeter, Receiver

MODEL 4160series (416B, 416C, 416D, 416K)

  • ■ DIN size 72×36 mm Compact size series
  • ■ Available with scaling function
  • ■ Available with many output options

Operation manual

Standard Specifications

Model Designation

416 □-□ - -
└①┘

①Input Specification / Measuring Range

DC Input
【 DC Voltage Measurement 】
Code Measuring Range Input Resistance Accuracy *1 Overload
D-02 ±99.99mV 100MΩ ±(0.05% of rdg + 3digit) DC±250V
D-03 ±999.9mV 1MΩ ±(0.05% of rdg + 3digit) DC±250V
D-04 ±9.999 V 1MΩ ±(0.05% of rdg + 3digit) DC±250V
D-05 ±99.99 V 1MΩ ±(0.05% of rdg + 3digit) DC±250V
【 DC Current Measurement 】
Code Measuring Range Input Resistance Accuracy *1 Overload
D-12 ±99.99μA 1KΩ ±(0.1% of rdg + 3digit) DC ± 10 mA
D-13 ±999.9μA 100Ω ±(0.1% of rdg + 3digit) DC ± 50 mA
D-14 ±9.999mA 10Ω ±(0.1% of rdg + 3digit) DC ±150 mA
D-15 ±99.99mA ±(0.1% of rdg + 3digit) DC ±500 mA
D-16 ±999.9mA 0.1Ω ±(0.15% of rdg +5digit) DC ±3 A
Temperature coefficient (*2):
416D-02 to -05, -12 to -15...±150 ppm/°C
416D-16......................±200 ppm/°C
Receiver Input
Code Measuring Range Input Resistance Accuracy *1 Overload
C-09 DC 1 to 5 V 1MΩ ±(0.1% of rdg + 3 digit) DC ±250 V
C-19 DC 4 to 20 mA 25Ω ±(0.1% of rdg + 3digit) DC ±100 mA
C-V1 DC 0 to 1 V 1MΩ ±(0.1% of rdg + 3digit) DC ±250 V
C-V2 DC 0 to 5 V 1MΩ ±(0.1% of rdg + 3digit) DC ±250 V
C-V3 DC 0 to 10 V 1MΩ ±(0.1% of rdg + 3digit) DC ±250 V
C-A1 DC 0 to 1 mA 100Ω ±(0.1% of rdg + 3digit) DC ±50 mA
Temperature coefficient (*2):
±150 ppm/°C
AC Input (Average Value)
【 AC Voltage Measurement 】
Code Measuring Range Input Resistance Accuracy *1 Overload
B-22 AC 99.99mV 1MΩ ±(0.1% of rdg + 10digit) AC 100 V
B-23 AC 999.9mV 1MΩ ±(0.1% of rdg + 10digit) AC 100 V
B-24 AC 9.999 V 1MΩ ±(0.1% of rdg + 10digit) AC 250 V
B-25 AC 99.99 V 1MΩ ±(0.1 % of rdg +10digit) AC 250 V
B-26 AC 699.9 V  10MΩ ±(0.2 % of rdg +10digit) AC 700 V
【 AC Current Measurement 】
Code Measuring Range Input Resistance Accuracy *1 Overload
B-32 AC 99.99 µA 1KΩ ±(0.1% of rdg + 20digit) AC 10mA
B-33 AC 999.9 μA 100Ω ±(0.1% of rdg + 20digit) AC 50mA
B-34 AC 9.999 mA 10Ω ±(0.1 % of rdg +20digit) AC150mA
B-35 AC 99.99 mA ±(0.1 % of rdg +20digit) AC500mA
B-36 AC 999.9 mA 0.1Ω ±(0.2 % of rdg +20digit)  AC   3A
B-37 AC 5.000 A 0.01Ω ±(0.2 % of rdg +20digit) AC   7A
Temperature coefficient (*2):
±300 ppm/°C,
Frequency range:
Sine wave of 40 Hz to 1 kHz
AC Input (Real Effective Value)
【 AC Voltage Measurement 】
Code Measuring Range Input Resistance Accuracy *3 Overload
K-22 AC 99.99 mV 1MΩ ±(0.1% of rdg + 10digit) AC 100 V
K-23 AC 999.9mV 1MΩ ±(0.1% of rdg + 10digit) AC 100 V
K-24 AC 9.999 V 1MΩ ±(0.1% of rdg + 10digit) AC 250 V
K-25 AC 99.99 V 1MΩ ±(0.1 % of rdg +10digit) AC 250 V
K-26 AC 699.9 V  10MΩ ±(0.2 % of rdg +10digit) AC 700 V
【 AC Current Measurement 】
Code Measuring Range Input Resistance Accuracy *3 Overload
K-32 AC 99.99μA 1KΩ ±(0.1% of rdg + 20digit) AC 10 mA
K-33 AC 999.9μA  100Ω ±(0.1% of rdg + 20digit) AC 50 mA
K-34 AC 9.999mA 10Ω ±(0.1 % of rdg +20digit) AC 150 mA
K-35 AC 99.99mA ±(0.1 % of rdg +20digit) AC 500 mA
K-36 AC 999.9mA 0.1Ω ±(0.2 % of rdg +20digit) AC 3 A
K-37 AC 5.000A  0.01Ω ±(0.2 % of rdg +20digit) AC 7 A
*Temperature coefficient:
±300 ppm/°C,
Frequency range:
Sine wave of 40 Hz to 1 kHz

②Supply Voltage

Code Power Source Voltage
3 AC 100 V (90 to 132 V)
5 AC 200 V (180 to 264 V)
B DC 9 to 32 V

③Data Output

Code Specifications Output Impedance Allowable Load Resistance
Blank For display only
03 Analog output DC 0 to 1 V Less than 0.1 Ω More than 1 kΩ
04 Analog output DC 0 to 5 V Less than 0.1 Ω  More than 5 kΩ
05 Analog output DC 0 to 10 V Less than 0.1 Ω More than 10 kΩ
09 Analog output DC 1 to 5 V Less than 0.1 Ω  More than 5 kΩ
23 Analog output DC 0 to 1 mA More than 5 MΩ 0 to 5 kΩ
29 Analog output DC 4 to 20 mA More than 5 MΩ 0 to 250 Ω
BP BCD output  (TTL level: positive logic)  
BN BCD output  (TTL level: negative logic)
DN BCD output (Transistor output source type)
CP High, low limit comparator output
*1 Accuracy : Defined at 23 ± 5°C, 45 to 75% RH
*2 Temperature coefficient : Temperature application range 0 to 50°C
*3 Accuracy : Defined at 23 ± 5°C, 45 to 75% RH
However, it is only applicable to the more than 5% of sine wave input of the full scale.
(Crest factor: 4, In case of 416K–37 is 2)
(Peak value up to 1000 V for 416K-26)

General Specifications

Display 0 – 9999 red LED (character height 15 mm), with zero-suppress function.
Over-range indication: Display flashes with 4 digit when exceeds 9999.
Decimal Point: Adjustment of optional setting is available from the panel front.
Scaling function Refer the operation manual.
Hold function Holds display value (BCD output and RS-483 output)
Sampling rate Approximately 2.5 times/sec.
Input configuration Single ended, floating input
A/D conversion Dual slope integration system
Noise rejection Normal mode (NMR): More than 50 dB (Except AC input)
Common mode (CMR): More than 110 dB (Except AC input)
Power source line mixing noise: 1000 V
Withstand voltage Input terminals - COM of each output: AC 500 V for 1min.
Input / output terminals - Power source terminals: AC 1500 V for 1min. (*)
Power source terminals – External case: AC 1500 V for 1min.
(*): AC 1000 V in case of DC power source.
Insulation resistance DC 500 V More than 100 MΩ
Power source voltage AC power source voltage: AC90-132V or AC180-264V 50/60Hz
DC power source voltage: DC9-32V
Power consumption Approx. 2 VA with AC 100 V
Approx. 170 mA with DC 12 V
Approx. 100 mA with DC 24 V
Operating temperature 0 to 50°C
Storage temperature -20 to 70°C
Weight AC power source models Approx. 260 g
DC power source models Approx. 200 g

page top